Oil-immersed Ground Transformer direct supply-10.5kV 35kV

  • Oil-immersed Ground Transformer direct supply-10.5kV 35kV
Key attributes
Brand Vziman
Model NO. Oil-immersed Ground Transformer direct supply-10.5kV 35kV
Rated voltage 35kV
Rated frequency 50/60Hz
Rated capacity 400kVA
Series DKS
Product descriptions from the supplier
Description

35kV Oil-immersed Grounding transformer Product introduction

35kV Oil-immersed Grounding transformer is commonly used to provide an artificial loaded neutral point for the ungrounded point of the system for system grounding. The neutral point of this product is connected to the arc suppression coil or resistor, and then grounded. A secondary winding with a continuous rated capacity can be used as a power source for the station.

35kV Oil-immersed Grounding transformer Product use

Substations, user distribution stations and other 35kV and below power systems.

35kV Oil-immersed Grounding transformer Main technical parameters

  • Rated capacity:100 ~ 5500kVA;
  • Rated voltage: 35kVand below;
  • Insulation class: Class A;
  • Standard basis: GB1094.6;
  • Ambient temperature: -25 ~ +40℃;
  • The relative air temperature: the daily average does not exceed 95%, the monthly average does not exceed 90%;
  • Altitude; Less than 1000m;
  • The ground inclination is not more than 3, with good grounding network;
  • Workplace: no fire, explosion risk, no conductive dust, no violent vibration, should leave enough space required by the device.

10kV series oil-immersed grounding transformer technical parameters table

Type

Connection

group

tapping range

Zero-sequence

Reactance

(Ω / phase)

Mounting hole

(transverse × vertical)4×18

Body size(length × width×height)mm

Body weight

(kg)

DKS-150/10.5

Zn

10.5

19

550×590

1150×650×896

500

DKS-200/10.5

Zn

10.5

14

550×640

1150×700×1113

760

DKS-200/10.5-100/0.4

Znyn11

10.5±2×2.5%/0.4

14

550×640

1150×700×1113

820

DKS-315/10.5

Zn

10.5

9

550×690

1230×750×1176

910

DKS-330/10.5-150/0.4

Znyn11

10.5±2×2.5%/0.4

9

550×690

1230×750×1206

950

DKS-400/10.5

Zn

10.5

6

550×690

1250×750×1181

1050

DKS-400/10.5-100/0.4

Znyn11

10.5±2×2.5%/0.4

6

550×690

1250×750×1211

1100

DKS-500/10.5

Zn

10.5

6

550×690

1300×750×1181

1100

DKS-500/10.5-100/0.4

Znyn11

10.5±2×2.5%/0.4

6

550×690

1300×750×1250

1150

DKS-630/10.5

Zn

10.5

4

550×790

1350×850×1250

1350

DKS-630/10.5-200/0.4

Znyn11

10.5+2×2.5%/0.4

4

550×790

1350×850×1286

1400

DKS-800/10.5

Zn

10.5

4

550×790

1400×850×1295

1460

DKS-800/10.5-100/0.4

Znyn11

10.5+2×2.5%/0.4

4

550×790

1400×850×1304

1500

DKS-1000/10.5

Zn

10.5

3

550×790

1450×850×1408

1820

DKS-1000/10.5-100/0.4

Znyn11

10.5±2×2.5%/0.4

3

550×790

1450×850×1450

1900

Note: The dimensions are for reference only and are subject to the actual drawings and dimensions provided.

Technical parameter table of 35kV series oil-immersed grounding transformer

Type

Connection group

lap range

Zero-sequence

Reactance

(Ω / phase)

gauge

Body size

(length×width×height mm)

Body weigh

(kg)

DKS-400/35

Znyn11

35±2×2.5%

144

1070×1080

2100×1200×1465

2000

DKS-500/35

Znyn11

35±2×2.5%

123

1070×1080

2140×1200×1505

2100

DKS-630/35

Zn

35±2×2.5%

119

1070×1080

2220×1200×1588

2520

DKS-630/35-250/0.4

Znyn11

35±2×2.5%/0.4

89

1070×1080

2240×1200×1680

2700

DKS-700/35

Znyn11

35±2×2.5%

98

1070×1080

2240×1200×1635

2600

DKS-700/35-315/0.4

Znyn11

35±2×2.5%/0.4

79

1070×1080

2350×1200×1555

3050

DKS-800/35-250/0.4

Znyn11

35±2×2.5%/0.4

85

1070×1080

2240×1200×1805

2900

DKS-1000/35-250/0.4

Znyn11

35±2×2.5%/0.4

80

1070×1080

2250×1200×1860

3050

DKS-1000/35-315/0.4

Znyn11

35±2×2.5%/0.4

75

1070×1080

2420×1200×1795

3350

DKS-1250/35-250/0.4

Znyn11

35±2×2.5%/0.4

82

1070×1080

2300×1200×1935

3500

DKS-1700/35-250/0.4

Znyn11

35±2×2.5%/0.4

68

1070×1080

2520×1200×1945

4150

DKS-2000/35

Zn

35±2×2.5%

54

1070×1080

2530×1200×1945

4450

DKS-2400/35-400/0.4

Znyn11

35±2×2.5%/0.4

44

1070×1130

2600×1250×2007

5000

DKS-2500/35

Zn

35±2×2.5%

40

1070×1130

2600×1250×2007

5100

Note: The dimensions are for reference only and are subject to the actual drawings and dimensions provided.

Documentation Resource Library
Vziman IEC/ ANSI Oil-immersed Grounding Transformer selection catalog
Restricted.
Vziman IEC/ ANSI Oil-immersed Grounding Transformer selection catalog
Catalogue
English
Consulting
Consulting
Send inquiry
+86
Click to upload file
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.