| Brand | Vziman |
| Model NO. | Oil-immersed Ground Transformer direct supply-10.5kV 35kV |
| Rated voltage | 10.5KV |
| Rated frequency | 50/60Hz |
| Rated capacity | 400kVA |
| Series | DKS |
35kV Oil-immersed Grounding transformer Product introduction
35kV Oil-immersed Grounding transformer is commonly used to provide an artificial loaded neutral point for the ungrounded point of the system for system grounding. The neutral point of this product is connected to the arc suppression coil or resistor, and then grounded. A secondary winding with a continuous rated capacity can be used as a power source for the station.
35kV Oil-immersed Grounding transformer Product use
Substations, user distribution stations and other 35kV and below power systems.
35kV Oil-immersed Grounding transformer Main technical parameters
10kV series oil-immersed grounding transformer technical parameters table
|
Type |
Connection group |
tapping range |
Zero-sequence Reactance (Ω / phase) |
Mounting hole (transverse × vertical)4×18 |
Body size(length × width×height)mm |
Body weight (kg) |
|
DKS-150/10.5 |
Zn |
10.5 |
19 |
550×590 |
1150×650×896 |
500 |
|
DKS-200/10.5 |
Zn |
10.5 |
14 |
550×640 |
1150×700×1113 |
760 |
|
DKS-200/10.5-100/0.4 |
Znyn11 |
10.5±2×2.5%/0.4 |
14 |
550×640 |
1150×700×1113 |
820 |
|
DKS-315/10.5 |
Zn |
10.5 |
9 |
550×690 |
1230×750×1176 |
910 |
|
DKS-330/10.5-150/0.4 |
Znyn11 |
10.5±2×2.5%/0.4 |
9 |
550×690 |
1230×750×1206 |
950 |
|
DKS-400/10.5 |
Zn |
10.5 |
6 |
550×690 |
1250×750×1181 |
1050 |
|
DKS-400/10.5-100/0.4 |
Znyn11 |
10.5±2×2.5%/0.4 |
6 |
550×690 |
1250×750×1211 |
1100 |
|
DKS-500/10.5 |
Zn |
10.5 |
6 |
550×690 |
1300×750×1181 |
1100 |
|
DKS-500/10.5-100/0.4 |
Znyn11 |
10.5±2×2.5%/0.4 |
6 |
550×690 |
1300×750×1250 |
1150 |
|
DKS-630/10.5 |
Zn |
10.5 |
4 |
550×790 |
1350×850×1250 |
1350 |
|
DKS-630/10.5-200/0.4 |
Znyn11 |
10.5+2×2.5%/0.4 |
4 |
550×790 |
1350×850×1286 |
1400 |
|
DKS-800/10.5 |
Zn |
10.5 |
4 |
550×790 |
1400×850×1295 |
1460 |
|
DKS-800/10.5-100/0.4 |
Znyn11 |
10.5+2×2.5%/0.4 |
4 |
550×790 |
1400×850×1304 |
1500 |
|
DKS-1000/10.5 |
Zn |
10.5 |
3 |
550×790 |
1450×850×1408 |
1820 |
|
DKS-1000/10.5-100/0.4 |
Znyn11 |
10.5±2×2.5%/0.4 |
3 |
550×790 |
1450×850×1450 |
1900 |
Note: The dimensions are for reference only and are subject to the actual drawings and dimensions provided.
Technical parameter table of 35kV series oil-immersed grounding transformer
|
Type |
Connection group |
lap range |
Zero-sequence Reactance (Ω / phase) |
gauge |
Body size (length×width×height mm) |
Body weigh (kg) |
|
DKS-400/35 |
Znyn11 |
35±2×2.5% |
144 |
1070×1080 |
2100×1200×1465 |
2000 |
|
DKS-500/35 |
Znyn11 |
35±2×2.5% |
123 |
1070×1080 |
2140×1200×1505 |
2100 |
|
DKS-630/35 |
Zn |
35±2×2.5% |
119 |
1070×1080 |
2220×1200×1588 |
2520 |
|
DKS-630/35-250/0.4 |
Znyn11 |
35±2×2.5%/0.4 |
89 |
1070×1080 |
2240×1200×1680 |
2700 |
|
DKS-700/35 |
Znyn11 |
35±2×2.5% |
98 |
1070×1080 |
2240×1200×1635 |
2600 |
|
DKS-700/35-315/0.4 |
Znyn11 |
35±2×2.5%/0.4 |
79 |
1070×1080 |
2350×1200×1555 |
3050 |
|
DKS-800/35-250/0.4 |
Znyn11 |
35±2×2.5%/0.4 |
85 |
1070×1080 |
2240×1200×1805 |
2900 |
|
DKS-1000/35-250/0.4 |
Znyn11 |
35±2×2.5%/0.4 |
80 |
1070×1080 |
2250×1200×1860 |
3050 |
|
DKS-1000/35-315/0.4 |
Znyn11 |
35±2×2.5%/0.4 |
75 |
1070×1080 |
2420×1200×1795 |
3350 |
|
DKS-1250/35-250/0.4 |
Znyn11 |
35±2×2.5%/0.4 |
82 |
1070×1080 |
2300×1200×1935 |
3500 |
|
DKS-1700/35-250/0.4 |
Znyn11 |
35±2×2.5%/0.4 |
68 |
1070×1080 |
2520×1200×1945 |
4150 |
|
DKS-2000/35 |
Zn |
35±2×2.5% |
54 |
1070×1080 |
2530×1200×1945 |
4450 |
|
DKS-2400/35-400/0.4 |
Znyn11 |
35±2×2.5%/0.4 |
44 |
1070×1130 |
2600×1250×2007 |
5000 |
|
DKS-2500/35 |
Zn |
35±2×2.5% |
40 |
1070×1130 |
2600×1250×2007 |
5100 |
Note: The dimensions are for reference only and are subject to the actual drawings and dimensions provided.