Oil immersed transformers have stable and reliable insulation performance, effectively avoiding voltage fluctuations and interference. They have strong overload capacity, small size, light weight, and low operating noise. Not only are they easy to transport and install, but they can also reduce production and operating costs. They are high-performance distribution transformers.

1. Windings

The high and low voltage coils are wound using copper conductors, copper foil, and insulating materials. After being preheated and dried, they undergo vacuum drying in a vacuum drying device to remove moisture and gas from the insulation.They exhibit strong resistance to short-term overload.

2. Insulation

Between the layers of high and low voltage windings, pure natural wood fiber modified point glue paper is used, which can operate safely at 130°C; after winding completion, it undergoes thermal setting, forming a solid and rigid whole; The core body adopts a hybrid insulation system, with overall spacer blocks compressed to ensure the oil passages are unobstructed while enhancing the tight fit between the windings, core, and clamps. The core body is equipped with a positioning structure to prevent displacement during transportation. Additionally, all fasteners are fitted with lock nuts to ensure they do not loosen during long-term operation, meeting the requirement of a non-suspended core.

3. Core

The core utilizes high-quality, high-permeability, cold-rolled grain-oriented silicon steel sheets, with their surfaces covered by anti-corrosion insulating coatings. The silicon steel sheets undergo a 45-degree full oblique shear, and the joints between the core column and the yoke adopt a 7-step laminated structure. Simultaneously, the flatness of the silicon steel sheets is enhanced, and appropriate clamping force is applied to the iron core, effectively reducing transformer noise.

Product Standards

IEC 60076 - Power transformers – Part 1: General; Part 2: Temperature rise; Part 3: Insulation levels, dielectric tests and external clearances in air; Part 4: Guide to lightning-impulse and switching-impulse testing; Part 5: Ability to withstand short circuit; Part 7: Loading guide for oil-immersed power transformers; Part 10: Determination of sound levels; Part 20: Energy efficiency for liquid-immersed power transformers.

IEC 60214 - Tap-changers – Part 1: Performance requirements and test methods; Part 2: Application guide

IEC 60437 - Radio interference test on high-voltage insulators

IEC 60507 - Artificial pollution tests on high-voltage insulators to be used on a.c. systems

IEC 60137 - Insulated bushings for alternating voltages above 1 000 V

IEC 60404-1   - Magnetic Materials classifications

ANSI C57 12.90   - Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers

IEC 60296 - Fluids for electrotechnical applications – Unused mineral insulating oils for transformers and switchgear

EN 50464-4 - Three-phase oil-immersed distribution transformers 50 Hz, 50 kVA to 2 500 kVA – Part 4: Requirements and tests for higher-loss transformers (HL) and higher-loss-high-short-circuit transformers (HLH)

10kV S13-M-30~2500/10 Transformer Technical Data

Model No-load Loss(W) Short-circuit Impedance(%) No-loadCurrent(%) Total Weight(kg) Oil Weight(kg) Dimensions (mm) Track Gauge (Transverse × Longitudinal)
Length Width Height
S13-M-25/10 90 4 1.2 243 60 680 500 860 300×400
S13-M-50/10 130 1.04 307 67 725 630 865 300×400
S13-M-63/10 150 0.96 360 78 730 640 890 300×400
S13-M-80/10 180 0.96 427 85 755 690 920 400×500
S13-M-100/10 200 0.88 513 95 765 710 930 400×500
S13-M-125/10 240 0.88 593 110 795 740 945 400×500
S13-M-160/10 280 0.8 680 125 835 790 980 400×500
S13-M-200/10 340 0.8 787 140 1130 770 1010 400×500
S13-M-300/10 450 0.72 1020 178 1250 880 1070 550×660
S13-M-315/10 480 0.72 1607 180 1300 900 1070 550×660
S13-M-400/10 570 0.64 1293 206 1325 915 1095 550×660
S13-M-500/10 680 0.64 1507 235 1450 1020 1140 550×660
S13-M-630/10 810 0.48 1733 270 1540 1100 1150 660×820
S13-M-800/10 980 5 0.48 2093 310 1580 1120 1190 660×820
S13-M-1000/10 1150 0.48 2387 354 1610 1150 1250 660×820
S13-M-1250/10 1360 0.4 2840 420 1660 1190
1300
 660×820
S13-M-1500/10 1500 6 0.4 2890 490 1680 1200 1380 820×820
S13-M-1600/10 1640 0.4 3387 510 1710 1210 1430 820×820
S13-M-2000/10 1940 0.32 4160 600 1810 1300 1450 820×820
S13-M-2500/10 2290 0.32 4840 684 1930 1400 1530 820×820
S13-M-3000/10 2800 7 0.65 4400 900 2000 1500 1800 820×820
S13-M-3500/10 3200 0.60 4700 950 2080 1550 1850 820×820
S13-M-4000/10 3600 0.55 5200 1000 2150 1650 1950 820×820
S13-M-5000/10 4200 0.50 5900 1150 2450 1800 2050 820×820

The data listed in the table above is for reference only, and the final data shall be subject to actual production.

Documentation Resource Library
Vziman IEC/ ANSI Oil-immersed Power transformer selection catalog
Restricted.
Vziman IEC/ ANSI Oil-immersed Power transformer selection catalog
Catalogue
English
Consulting
Consulting
FAQ
Q: What is a 10kV oil-immersed power transformer?
A:

A 10kV oil-immersed power transformer is a type of electrical transformer that operates at 10,000 volts. It uses oil for insulation and cooling. This design helps keep the transformer running efficiently while also protecting it from overheating. These transformers are commonly used in power distribution systems.

Q:How does an 10kV oil-immersed power transformer work?

A:10kV oil-immersed power transformer work by using electrical currents to create a magnetic field that transfers energy between the high and low voltage wires. The oil inside helps cool the transformer and insulates the electrical parts, keeping everything safe and functioning properly.

Q:What are the benefits of using an 10kV oil-immersed power transformer?

A:10kV oil-immersed power transformer offer several benefits, including better cooling, reduced noise when operating, and a design that minimizes electrical interference. They are also smaller and lighter than some alternatives, making them easier to install.

Q:What materials are used in the windings of a 10kV oil-immersed power transformer?

A:The windings in a 10kV oil-immersed power transformer are typically made of copper or aluminum wire. This wire is insulated to prevent electrical shorts and help maintain safety in operation. The choice of materials helps ensure the transformer can handle its electrical load.

Related Products

Related Solutions

Send inquiry
+86
Click to upload file
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.