| Brand | Vziman |
| Model NO. | Oil-immersed Neutral Earthing Transformer-34.5kV 35kV 36kV |
| Rated voltage | 36kV |
| Rated frequency | 50/60Hz |
| Cooling mode | ONAN |
| Series | DKSC |
| Neutra Earthing Transformer Technical Specifications | |
| Type | Oil-type: up to 123 kV (BIL: 450 kV class) Dry-type: up to 36 kV (BIL: 170 kV class) With auxiliary winding on request. |
| Power | up to 2000kVA |
| Voltage | up to 36kV |
| Current | 3000A |
| Duty seconds | 10/30/60 or others |
| Cooling method | ONAN, AF |
| Frequency | 50/60Hz |
| Transformer oil | Mineral oil, FR3 oil, Silicon oil ,Midel 7131 and other oil as required by customers |
| Paint corrosion resistance | C4 and C5-M |
| Standard | IEC , AS, EN, IEEE, GOST |
| Vertor group | ZNyn1 ZIAZIG ZN0 zyn11 |
| Installation | indoor /outdoor |
| Ambient Temperature | -30 +55 ℃ |
Oil-immersed Neutral Earthing transformer, the design have Variable shape,Terminal Box Can design from Top also can from side.The Netural Bushing can be also in the same termimal with HV
Oil-immersed Neutral Earthing Transformer Design and modeling diversification

It is widely used in medium and high-voltage power systems (such as 10kV, 35kV, 66kV, 110kV) that adopt ungrounded, impedance-grounded or arc-suppression-coil-grounded neutral point modes, effectively improving the system's ground fault handling capability.
Q:What routine tests are required for neutral earthing transformers before commissioning?
A:Pre-commissioning tests include insulation resistance measurement, dielectric loss tangent test, winding resistance measurement, short-circuit impedance test, oil chromatography analysis and lightning impulse test, to verify the electrical performance and safety of the transformer.
Q:Can an neutral earthing transformer be customized to meet the requirements of a specific power system?
A:Yes. Professional manufacturers can customize parameters such as rated capacity, tap position, tank structure, and protection device configuration according to the system's voltage level, fault current characteristics, and installation environment to achieve optimal matching.