| Marque | Vziman |
| Numéro de modèle | Customization 11kV 20kV 24kV 33kV Three Phase Oil Immersed Distribution Transformer |
| tension nominale | 24kV |
| fréquence nominale | 50/60Hz |
| capacité nominale | 500kVA |
| Série | S |
Principaux Paramètres Techniques
|
Rated capacity(KVA)
|
High Voltage(KV)
|
H.V. Tap Range
|
Low Voltage(KV)
|
Connection Symbol
|
Short Circuit Impendence(%)
|
No-Load Loss(W)
|
On-Load Loss(W)
|
No Load Current(%)
|
|
50
|
11kV
20kV
22kV
24kV 33kV
|
±5%±2×2.5%
|
0.4
|
Dyn11Yyn0
|
6
|
380
|
1300
|
2.4
|
|
100
|
600
|
2100
|
2.2
|
|||||
|
160
|
750
|
2600
|
1.8
|
|||||
|
200
|
820
|
3100
|
1.8
|
|||||
|
250
|
940
|
3600
|
1.6
|
|||||
|
315
|
1080
|
4300
|
1.6
|
|||||
|
400
|
1280
|
5100
|
1.4
|
|||||
|
500
|
1500
|
6100
|
1.4
|
|||||
|
630
|
1700
|
7200
|
1.2
|
|||||
|
800
|
1950
|
8700
|
1.2
|
|||||
|
1000
|
2300
|
10300
|
1.0
|
|||||
|
1250
|
2650
|
12150
|
1.0
|
|||||
|
1600
|
3100
|
14600
|
1.0
|
|||||
|
2000
|
3600
|
17250
|
0.8
|
|||||
|
2500
|
4300
|
20400
|
0.8
|
|||||
|
2000
|
8
|
3600
|
18800
|
0.8
|
||||
|
2500
|
4300
|
22400
|
0.8
|

Produire un certificat
Si les ventilateurs ou les pompes à huile cessent de fonctionner, vérifiez immédiatement l’alimentation électrique et le circuit de commande. Démarrez l’équipement de refroidissement de secours si disponible. Réduisez la charge du transformateur pour abaisser la température ; arrêtez immédiatement si la température du haut de l’huile dépasse 95℃ pour éviter des dommages à l’isolation dus à une surchauffe.
Les facteurs clés incluent le fonctionnement en surcharge à long terme (accélère le vieillissement de l'isolation), une qualité d'huile médiocre (oxydation ou intrusion d'humidité), un environnement défavorable (corrosion, forte humidité), des surtensions fréquentes et un entretien insuffisant. Un contrôle adéquat de la charge et un entretien régulier peuvent prolonger sa durée de vie jusqu'à 20-30 ans.